Alco Controls Components for / Technical Bulletin R404A is one of the most commonly used refrigerant today. However, many end-users, equipment and compressor manufacturers are investigating ways to minimize their impact on the environment. Improving system architectures, using a refrigerant with lower global warming potential (GWP) can significantly improve the carbon footprint of an installation. Majority of Alco Controls products are released for refrigerants and. This document provides only the recently established nominal capacities as well as correction factors for selection of products in conjunction with and. It complements the general catalogue, technical bulletins and data sheets, where all other technical information of products are covered. For other operating conditions the selection tool Copeland Select will be available, (see www.emersonclimate.eu) or use correction factors with following formula: Q n = Q o x K t x K p Q n: Nominal valve capacity Q o: Required cooling capacity K t: Correction factor for evaporating and liquid temperature K p: Correction factor for pressure drop at valve Electronic Expansion Valves: Pulse Width Modulated Electronic Expansion Valve Nominal capacity, kw Type / Orifice EX2-00X 0.9 1 EX2-000 1.6 1.8 EX2-001 3.2 3.6 EX2-002 4.2 4.8 EX2-003 7.1 8 EX2-004 10.7 12.2 EX2-I/M00 16.9 19.2 High Performance Stepper Motor Driven Electrical Control Valves Type EX4 16.2 18.4 EX5 49 56 EX6 118 134 EX7 325 369 EX8 866 984 Nominal capacity at +38 C condensing temperature. +4 C evaporating temperature and 1 K subcooling EX2 EX5 EX4 EX6 Following valve drivers are available for the Electronic Expansion Valves EX4, EX5, EX6, EX7, EX8: EC3-X33/-X32 Superheat Controller EXD-U00 Universal Driver Module EX7 EX8 For more information, please consult technical bulletin, datasheet, operating instructions or catalogue (www.emersonclimate.eu).
Electronic Expansion Valves Liquid temp. C Correction factors K t Dew Bubble Evaporating temperature, C point point +20 +15 +10 +5 0-5 -10-15 -20-25 -30-35 -40-45 68 65 1.54 1.58 1.61 1.65 1.69 1.74 1.79 1.84 1.90 1.97 2.04 2.12 2.21 2.30 63 60 1.37 1.40 1.43 1.46 1.49 1.53 1.57 1.61 1.66 1.71 1.76 1.83 1.89 1.96 59 55 1.24 1.26 1.29 1.31 1.34 1.37 1.40 1.44 1.48 1.52 1.56 1.61 1.66 1.72 54 50 1.14 1.16 1.18 1.20 1.22 1.25 1.27 1.30 1.34 1.37 1.41 1.45 1.49 1.54 49 45 1.05 1.07 1.09 1.10 1.12 1.15 1.17 1.19 1.22 1.25 1.28 1.31 1.35 1.39 44 40 0.98 0.99 1.01 1.02 1.04 1.06 1.08 1.10 1.13 1.15 1.18 1.21 1.24 1.27 39 35 0.92 0.93 0.94 0.96 0.97 0.99 1.01 1.03 1.05 1.07 1.09 1.12 1.14 1.17 35 30 0.86 0.87 0.89 0.90 0.91 0.93 0.94 0.96 0.98 1.00 1.02 1.04 1.06 1.09 30 25 0.82 0.83 0.84 0.85 0.86 0.87 0.89 0.90 0.92 0.94 0.95 0.97 0.99 1.02 25 20 0.77 0.78 0.79 0.80 0.81 0.83 0.84 0.85 0.87 0.88 0.90 0.92 0.93 0.95 20 15 0.74 0.74 0.75 0.76 0.77 0.78 0.80 0.81 0.82 0.83 0.85 0.87 0.88 0.90 15 10 0.70 0.71 0.72 0.73 0.74 0.75 0.76 0.77 0.78 0.79 0.81 0.82 0.83 0.85 10 5 0.67 0.68 0.69 0.69 0.70 0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 6 0 0.64 0.65 0.66 0.66 0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.74 0.75 0.77 1-5 0.62 0.62 0.63 0.64 0.64 0.65 0.66 0.67 0.68 0.69 0.70 0.71 0.72 0.73-4 -10 0.59 0.60 0.61 0.61 0.62 0.63 0.63 0.64 0.65 0.66 0.67 0.68 0.69 0.70 Correction factors K ΔP ΔP, bar 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,5 K ΔP 3,42 2,79 2,42 2,16 1,98 1,83 1,71 1,61 1,53 1,46 1,4 1,34 1,29 1,25 ΔP, bar 8 9 10 11 12 13 14 15 16 17 18 19 20 21 K ΔP 1,21 1,14 1,08 1,03 0,99 0,95 0,91 0,88 0,86 0,83 0,81 0,79 0,77 0,75 Liquid temp. C Correction factors K t Dew Bubble Evaporating temperature, C point point +20 +15 +10 +5 0-5 -10-15 -20-25 -30-35 -40-45 68 65 1.51 1.53 1.55 1.58 1.61 1.64 1.68 1.71 1.75 1.80 1.85 1.90 1.96 2.02 63 60 1.35 1.37 1.39 1.41 1.43 1.46 1.49 1.52 1.55 1.59 1.63 1.67 1.71 1.76 58 55 1.23 1.25 1.26 1.28 1.30 1.32 1.35 1.37 1.40 1.43 1.46 1.50 1.53 1.57 54 50 1.14 1.15 1.16 1.18 1.20 1.22 1.24 1.26 1.28 1.31 1.33 1.36 1.39 1.43 49 45 1.06 1.07 1.08 1.10 1.11 1.13 1.14 1.16 1.18 1.20 1.23 1.25 1.28 1.31 44 40 0.99 1.00 1.01 1.02 1.04 1.05 1.07 1.08 1.10 1.12 1.14 1.16 1.18 1.21 40 35 0.93 0.94 0.95 0.96 0.97 0.99 1.00 1.01 1.03 1.05 1.06 1.08 1.10 1.13 35 30 0.88 0.89 0.90 0.91 0.92 0.93 0.94 0.95 0.97 0.98 1.00 1.02 1.03 1.05 30 25 0.83 0.84 0.85 0.86 0.87 0.88 0.89 0.90 0.91 0.93 0.94 0.96 0.97 0.99 25 20 0.79 0.80 0.81 0.82 0.82 0.83 0.84 0.85 0.87 0.88 0.89 0.91 0.92 0.94 20 15 0.76 0.76 0.77 0.78 0.78 0.79 0.80 0.81 0.82 0.83 0.85 0.86 0.87 0.89 15 10 0.72 0.73 0.74 0.74 0.75 0.76 0.77 0.77 0.78 0.79 0.81 0.82 0.83 0.84 11 5 0.69 0.70 0.70 0.71 0.72 0.72 0.73 0.74 0.75 0.76 0.77 0.78 0.79 0.80 6 0 0.66 0.67 0.68 0.68 0.69 0.69 0.70 0.71 0.72 0.73 0.73 0.74 0.75 0.77 1-5 0.64 0.64 0.65 0.65 0.66 0.67 0.67 0.68 0.69 0.70 0.70 0.71 0.72 0.73-4 -10 0.62 0.62 0.62 0.63 0.63 0.64 0.65 0.65 0.66 0.67 0.68 0.68 0.69 0.70 Correction factors K ΔP ΔP, bar 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 KΔP 3.51 2.87 2.48 2.22 2.03 1.88 1.76 1.66 1.57 1.5 1.43 1.38 1.33 1.28 ΔP, bar 8 9 10 11 12 13 14 15 16 17 18 19 20 21 KΔP 1.24 1.17 1.11 1.06 1.01 0.97 0.94 0.91 0.88 0.85 0.83 0.81 0.79 0.77 2
Thermo Expansion Valves (-45 +20 C) T-Series TISE TILE T-Series:Nominal capacity, kw Orifice X22440-B1B 1.9 2.1 X22440-B2B 3.6 4.1 X22440-B3B 7.8 8.8 X22440-B3.5B 11.7 13.3 X22440-B4B 17 19.3 X22440-B5B 21.9 24.8 X22440-B6B 29.9 34 X22440-B7B 40.5 45.9 X22440-B8B 47 53 X11873-B4B 57 65 X11873-B5B 73 83 X9117-B6B 90 102 X9117-B7B 102 116 X9117-B8B 141 160 X9117-B9B 171 194 X9166-B10B 219 249 X9144-B11B 249 283 X9144-B13B 297 338 TI: Nominal capacity, kw Orifice TIO-00X 0.5 0.6 TIO-000 1.3 1.5 TIO-001 3.2 3.6 TIO-002 5.2 5.9 TIO-003 8.4 9.5 TIO-004 13.7 15.5 TIO-005 16.6 18.9 TIO-006 19.2 21.8 T-series/TI charge recommendation for /F Valve Charge Type Evaporating temperature T-Series and TI NW Liquid -45 to 0 C T-Series SW40 Gas MOP -45 to -18 C TI SAD-20 Adsorption MOP -45 to -27 C Remark: Please use above specified charges for retrofit and new installation. It is required the readjustment of factory setting of valves. T / TI: Nominal capacity at +38 C condensing temperature, +4 C evaporating temperature and 1 K subcooling For more information, please consult technical bulletin, datasheet, operating instructions or catalogue (www.emersonclimate.eu). 3
Correction Factors for Thermo -Expansion Valves Liquid Temp. C Correction factors K t Correction factors K t Dew point Bubble point Evaporating temperature, C Evaporating temperature, C 0-5 -10-15 -20-25 -30-35 -40-45 0-5 -10-15 -20-25 -30-35 -40-45 68 65 1.69 1.74 1.79 2.04 2.43 2.93 3.55 4.31 5.22 6.30 1.61 1.64 1.68 1.90 2.24 2.68 3.22 3.86 4.63 5.52 63 60 1.49 1.53 1.57 1.78 2.12 2.55 3.07 3.71 4.47 5.37 1.43 1.46 1.49 1.68 1.98 2.36 2.83 3.39 4.04 4.81 59 55 1.34 1.37 1.40 1.59 1.89 2.26 2.72 3.27 3.93 4.70 1.30 1.32 1.35 1.52 1.79 2.13 2.54 3.04 3.62 4.30 54 50 1.22 1.25 1.27 1.44 1.71 2.04 2.45 2.94 3.52 4.20 1.20 1.22 1.24 1.39 1.64 1.95 2.32 2.77 3.29 3.90 49 45 1.12 1.15 1.17 1.32 1.56 1.86 2.23 2.67 3.19 3.80 1.11 1.13 1.14 1.29 1.51 1.79 2.14 2.55 3.02 3.57 44 40 1.04 1.06 1.08 1.22 1.44 1.72 2.05 2.45 2.92 3.47 1.04 1.05 1.07 1.20 1.41 1.67 1.98 2.36 2.80 3.31 39 35 0.97 0.99 1.01 1.14 1.34 1.59 1.90 2.27 2.70 3.20 0.97 0.99 1.00 1.12 1.32 1.56 1.85 2.20 2.61 3.08 35 30 0.91 0.93 0.94 1.06 1.25 1.49 1.77 2.11 2.51 2.97 0.92 0.93 0.94 1.06 1.24 1.47 1.74 2.07 2.44 2.88 30 25 0.86 0.87 0.89 1.00 1.18 1.40 1.66 1.98 2.35 2.78 0.87 0.88 0.89 1.00 1.17 1.38 1.64 1.95 2.30 2.71 25 20 0.81 0.83 0.84 0.94 1.11 1.31 1.56 1.86 2.21 2.61 0.82 0.83 0.84 0.95 1.11 1.31 1.55 1.84 2.17 2.56 20 15 0.77 0.78 0.80 0.89 1.05 1.24 1.48 1.76 2.08 2.46 0.78 0.79 0.80 0.90 1.05 1.24 1.47 1.74 2.06 2.42 15 10 0.74 0.75 0.76 0.85 1.00 1.18 1.40 1.67 1.97 2.32 0.75 0.76 0.77 0.86 1.00 1.18 1.40 1.66 1.96 2.30 10 5 0.70 0.71 0.72 0.81 0.95 1.12 1.33 1.58 1.87 2.21 0.72 0.72 0.73 0.82 0.96 1.13 1.34 1.58 1.87 2.19 6 0 0.67 0.68 0.69 0.77 0.91 1.07 1.27 1.51 1.78 2.10 0.69 0.69 0.70 0.79 0.92 1.08 1.28 1.51 1.78 2.09 1-5 0.64 0.65 0.66 0.74 0.87 1.03 1.22 1.44 1.70 2.00 0.66 0.67 0.67 0.75 0.88 1.04 1.23 1.45 1.71 2.00-4 -10 0.62 0.63 0.63 0.71 0.83 0.98 1.17 1.38 1.63 1.92 0.63 0.64 0.65 0.72 0.84 1.00 1.18 1.39 1.64 1.92 Correction factors K ΔP ΔP. bar 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,5 KΔP 3,42 2,79 2,42 2,16 1,98 1,83 1,71 1,61 1,53 1,46 1,4 1,34 1,29 1,25 ΔP. bar 8 9 10 11 12 13 14 15 16 17 18 19 20 21 KΔP 1,21 1,14 1,08 1,03 0,99 0,95 0,91 0,88 0,86 0,83 0,81 0,79 0,77 0,75 Correction factors K ΔP ΔP. bar 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 KΔP 3.51 2.87 2.48 2.22 2.03 1.88 1.76 1.66 1.57 1.5 1.43 1.38 1.33 1.28 ΔP. bar 8 9 10 11 12 13 14 15 16 17 18 19 20 21 KΔP 1.24 1.17 1.11 1.06 1.01 0.97 0.94 0.91 0.88 0.85 0.83 0.81 0.79 0.77 Remark: In case of subcooling more than 15K, please use additionally the following correction factors: Subcooling 20K 30K 40K 50K 60K Correction factors 0.8 0.7 0.6 0.5 0.4 4
Thermo -Expansion Valves Series ZZ For Ultra Low Evaporating Temperatures (-80-45 C) Nominal capacity, kw Orifice X10-B01 1.7 2.0 X10-B02 3.6 4.2 X10-B03 6.1 7.0 X10-B04 9.7 11.2 X10-B05 14.6 16.9 X10-B06 19.4 22.5 X10-B07 24.2 28.1 Nominal capacity at +25 C condensing temperature. -40 C evaporating temperature and 1 K subcooling ZZ-Series charge recommendation for /F Charge Type Evaporating temperature SW40 Gas MOP -75 to -18 C Remark: Please use above specified charge for retrofit and new installation. It is required the readjustment of factory setting of valves. Correction Factors for ZZ Thermo -Expansion Valves Liquid temp. C Correction factors Kt Correction factors Kt Dew Bubble Evaporating temperature, C Evaporating temperature, C point point -40-45 -50-55 -60-65 -70-75 -40-45 -50-55 -60-65 -70-75 44 40 1.24 1.51 1.86 2.31 2.91 3.71 4.81 6.32 1.22 1.47 1.80 2.22 2.78 3.52 4.53 5.92 40 35 1.15 1.40 1.71 2.12 2.67 3.40 4.39 5.75 1.13 1.37 1.67 2.06 2.58 3.26 4.19 5.46 35 30 1.07 1.30 1.59 1.97 2.47 3.13 4.04 5.28 1.06 1.28 1.56 1.93 2.40 3.04 3.90 5.08 30 25 1.00 1.21 1.48 1.83 2.29 2.91 3.74 4.89 1.00 1.21 1.47 1.81 2.25 2.85 3.65 4.74 25 20 0.94 1.14 1.39 1.71 2.14 2.72 3.49 4.55 0.94 1.14 1.38 1.70 2.12 2.68 3.42 4.45 20 15 0.89 1.07 1.31 1.61 2.01 2.55 3.27 4.26 0.90 1.08 1.31 1.61 2.01 2.53 3.23 4.19 15 10 0.84 1.01 1.23 1.52 1.90 2.40 3.08 4.00 0.85 1.02 1.24 1.53 1.90 2.39 3.06 3.96 11 5 0.80 0.96 1.17 1.44 1.80 2.27 2.91 3.78 0.81 0.98 1.18 1.45 1.81 2.27 2.90 3.76 6 0 0.76 0.91 1.11 1.37 1.71 2.15 2.75 3.58 0.78 0.93 1.13 1.39 1.72 2.17 2.76 3.58 1-5 0.72 0.87 1.06 1.31 1.63 2.05 2.62 3.40 0.74 0.89 1.08 1.33 1.65 2.07 2.64 3.41-4 -10 0.69 0.83 1.01 1.25 1.55 1.95 2.50 3.23 0.71 0.85 1.04 1.27 1.58 1.98 2.52 3.26-9 -15 0.66 0.80 0.97 1.19 1.48 1.87 2.38 3.09 0.68 0.82 0.99 1.22 1.51 1.90 2.41 3.12-14 -20 0.64 0.77 0.93 1.14 1.42 1.79 2.28 2.95 0.66 0.79 0.96 1.17 1.45 1.82 2.32 2.99-19 -25 0.61 0.74 0.90 1.10 1.37 1.72 2.19 2.83 0.63 0.76 0.92 1.13 1.40 1.75 2.23 2.88-24 -30 0.59 0.71 0.86 1.06 1.31 1.65 2.10 2.72 0.61 0.73 0.89 1.09 1.35 1.69 2.14 2.77-29 -35 0.57 0.69 0.83 1.02 1.27 1.59 2.02 2.62 0.59 0.71 0.86 1.05 1.30 1.63 2.07 2.67-34 -40 0.55 0.66 0.80 0.98 1.22 1.53 1.95 2.52 0.57 0.69 0.83 1.01 1.25 1.57 2.00 2.57-39 -45 0.53 0.64 0.78 0.95 1.18 1.48 1.88 2.43 0.55 0.66 0.80 0.98 1.21 1.52 1.93 2.49-44 -50 0.52 0.62 0.75 0.92 1.14 1.43 1.82 2.35 0.54 0.64 0.78 0.95 1.17 1.47 1.87 2.40 Correction factors K ΔP ΔP. bar 0,5 1 1,5 2 3,5 4 4,5 5 5,5 6 6,5 7 K ΔP 4,81 3,4 2,77 2,4 1,82 1,7 1,6 1,52 1,45 1,39 1,33 1,28 ΔP. bar 8 9 10 11 12 13 14 15 16 17 18 19 K ΔP 1,2 1,13 1,07 1,02 0,98 0,94 0,91 0,88 0,85 0,82 0,8 0,78 Correction factors K ΔP ΔP. bar 0,5 1 1,5 2 3,5 4 4,5 5 5,5 6 6,5 7 K ΔP 4,92 3,48 2,84 2,46 1,86 1,74 1,64 1,56 1,48 1,42 1,37 1,32 ΔP. bar 8 9 10 11 12 13 14 15 16 17 18 19 K ΔP 1,23 1,16 1,1 1,05 1,01 0,97 0,93 0,9 0,87 0,84 0,82 0,8 Remark for Series ZZ: In case of subcooling more than 15K, please use additionally the following correction factors: Subcooling 20K 30K 40K 50K 60K Correction factors 0.8 0.7 0.6 0.5 0.4 5
Solenoid Valves Series 110RB, 200RB, 240RA, Normally Closed Nominal Capacity Liquid Line Duty kw Type Kv-Value m 3 /hr 110RB2 0.2 3.7 4.2 200RB3 0.4 7 7.9 200RB4 0.9 16.5 18.8 200RB6 1.6 29 33 240RA8 2.3 39 44 240RA9 4.8 81 92 240RA12 5.4 91 104 240RA16 8.8 148 168 240RA20 12.8 216 245 Nominal capacity at +38 C condensing temperature +4 C evaporating temperature, 1 K subcooling and 0.15 bar pressure drop 110RB 200RB For more information, please consult technical bulletin, datasheet, operating instructions or catalogue (www.emersonclimate.eu). 240RA Correction Factors for Solenoid Valves (Liquid Line Duty) Liquid temp. C Correction Factors K t Dew Bubble Evaporating Temperature, C point point 20 15 10 5 0-5 -10-15 -20-25 -30-35 -40-45 68 65 1.54 1.58 1.61 1.65 1.69 1.74 1.79 1.84 1.90 1.97 2.04 2.12 2.21 2.30 63 60 1.37 1.40 1.43 1.46 1.49 1.53 1.57 1.61 1.66 1.71 1.76 1.83 1.89 1.96 59 55 1.24 1.26 1.29 1.31 1.34 1.37 1.40 1.44 1.48 1.52 1.56 1.61 1.66 1.72 54 50 1.14 1.16 1.18 1.20 1.22 1.25 1.27 1.30 1.34 1.37 1.41 1.45 1.49 1.54 49 45 1.05 1.07 1.09 1.10 1.12 1.15 1.17 1.19 1.22 1.25 1.28 1.31 1.35 1.39 44 40 0.98 0.99 1.01 1.02 1.04 1.06 1.08 1.10 1.13 1.15 1.18 1.21 1.24 1.27 39 35 0.92 0.93 0.94 0.96 0.97 0.99 1.01 1.03 1.05 1.07 1.09 1.12 1.14 1.17 35 30 0.86 0.87 0.89 0.90 0.91 0.93 0.94 0.96 0.98 1.00 1.02 1.04 1.06 1.09 30 25 0.82 0.83 0.84 0.85 0.86 0.87 0.89 0.90 0.92 0.94 0.95 0.97 0.99 1.02 25 20 0.77 0.78 0.79 0.80 0.81 0.83 0.84 0.85 0.87 0.88 0.90 0.92 0.93 0.95 20 15 0.74 0.74 0.75 0.76 0.77 0.78 0.80 0.81 0.82 0.83 0.85 0.87 0.88 0.90 15 10 0.70 0.71 0.72 0.73 0.74 0.75 0.76 0.77 0.78 0.79 0.81 0.82 0.83 0.85 10 5 0.67 0.68 0.69 0.69 0.70 0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 6 0 0.64 0.65 0.66 0.66 0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.74 0.75 0.77 1-5 0.62 0.62 0.63 0.64 0.64 0.65 0.66 0.67 0.68 0.69 0.70 0.71 0.72 0.73-4 -10 0.59 0.60 0.61 0.61 0.62 0.63 0.63 0.64 0.65 0.66 0.67 0.68 0.69 0.70 and : Solenoid Valves (Liquid Line) Correction Factors K ΔP ΔP, bar 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75 K ΔP 1.73 1.22 1 0.87 0.77 0.71 0.65 0.61 0.58 0.55 0.52 0.5 0.48 0.46 0.45 6
Correction Factors for Solenoid Valves (Liquid Line Duty) Liquid temp. C Correction Factors K t Dew Bubble Evaporating Temperature, C point point 20 15 10 5 0-5 -10-15 -20-25 -30-35 -40-45 68 65 1.51 1.53 1.55 1.58 1.61 1.64 1.68 1.71 1.75 1.80 1.85 1.90 1.96 2.02 63 60 1.35 1.37 1.39 1.41 1.43 1.46 1.49 1.52 1.55 1.59 1.63 1.67 1.71 1.76 58 55 1.23 1.25 1.26 1.28 1.30 1.32 1.35 1.37 1.40 1.43 1.46 1.50 1.53 1.57 54 50 1.14 1.15 1.16 1.18 1.20 1.22 1.24 1.26 1.28 1.31 1.33 1.36 1.39 1.43 49 45 1.06 1.07 1.08 1.10 1.11 1.13 1.14 1.16 1.18 1.20 1.23 1.25 1.28 1.31 44 40 0.99 1.00 1.01 1.02 1.04 1.05 1.07 1.08 1.10 1.12 1.14 1.16 1.18 1.21 40 35 0.93 0.94 0.95 0.96 0.97 0.99 1.00 1.01 1.03 1.05 1.06 1.08 1.10 1.13 35 30 0.88 0.89 0.90 0.91 0.92 0.93 0.94 0.95 0.97 0.98 1.00 1.02 1.03 1.05 30 25 0.83 0.84 0.85 0.86 0.87 0.88 0.89 0.90 0.91 0.93 0.94 0.96 0.97 0.99 25 20 0.79 0.80 0.81 0.82 0.82 0.83 0.84 0.85 0.87 0.88 0.89 0.91 0.92 0.94 20 15 0.76 0.76 0.77 0.78 0.78 0.79 0.80 0.81 0.82 0.83 0.85 0.86 0.87 0.89 15 10 0.72 0.73 0.74 0.74 0.75 0.76 0.77 0.77 0.78 0.79 0.81 0.82 0.83 0.84 11 5 0.69 0.70 0.70 0.71 0.72 0.72 0.73 0.74 0.75 0.76 0.77 0.78 0.79 0.80 6 0 0.66 0.67 0.68 0.68 0.69 0.69 0.70 0.71 0.72 0.73 0.73 0.74 0.75 0.77 1-5 0.64 0.64 0.65 0.65 0.66 0.67 0.67 0.68 0.69 0.70 0.70 0.71 0.72 0.73-4 -10 0.62 0.62 0.62 0.63 0.63 0.64 0.65 0.65 0.66 0.67 0.68 0.68 0.69 0.70 and : Solenoid Valves (Liquid Line) Correction Factors K ΔP ΔP, bar 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75 K ΔP 1.73 1.22 1 0.87 0.77 0.71 0.65 0.61 0.58 0.55 0.52 0.5 0.48 0.46 0.45 7
Hermetic Liquid Line Filter Driers ADK ADK: Nominal Flow Capacity, kw Type Connection ODF Pressure drop Pressure drop 0.07 bar 0.14 bar 0.07 bar 0.14 bar ADK-032 6.3 9.2 7.0 10.2 ADK-032S ¼ 7.6 11.1 8.5 12.4 ADK-052 6.6 9.5 7.3 10.6 ADK-052S ¼ 9.3 14.8 10.4 16.5 ADK-053 12.2 18.4 13.6 20.5 ADK-053S 3 / 8 14.2 22.3 15.8 24.8 ADK-082 6.7 9.8 7.5 10.9 ADK-082S ¼ 10.3 15 11.5 16.7 ADK-083 14.4 20.8 16.0 23.1 ADK-083S 3 / 8 14.2 20.9 15.8 23.3 ADK-084 22.2 33.9 24.7 37.7 ADK-084S ½ 23.2 34.9 25.8 38.9 ADK-162 6.9 9.9 7.7 11.0 ADK-163 14.6 20.9 16.2 23.3 ADK-163S 3 / 8 16.3 23.2 18.1 25.8 ADK-164 30.6 42.4 34.1 47.2 ADK-164S ½ 31.5 43.2 35.1 48.1 ADK-165 38.8 57.6 43.2 64.1 ADK-165S 5 / 8 43 62.7 47.9 69.8 ADK-303 15.4 22 17.1 24.5 ADK-304 27.1 40.9 30.2 45.5 ADK-304S ½ 31.2 44.6 34.7 49.7 ADK-305 45.5 62.4 50.7 69.5 ADK-305S 5 / 8 41.7 63.2 46.4 70.3 ADK-307S 7 / 8 57.4 90.6 63.9 100.8 ADK-417S 7 / 8 71.9 109.3 80.0 121.7 ADK-757S 7 / 8 110.3 147.1 122.8 163.8 ADK-759S 1 1 / 8 120.3 155.6 133.9 173.2 FDB FDB: Nominal Flow Capacity, kw Type Connection ODF Pressure drop Pressure drop 0.07 bar 0.14 bar 0.07 bar 0.14 bar FDB-032 6 8.4 6.7 9.4 FDB-032S ¼ 9.2 13 10.2 14.5 FDB-052 6.1 8.8 6.8 9.8 FDB-052S ¼ 9.2 13 10.2 14.5 FDB-053 14.6 21 16.3 23.3 FDB-053S 3 / 8 18.3 26.1 20.3 29 FDB-082 6.4 9.3 7.1 10.3 FDB-082S ¼ 9.4 13.4 10.4 14.9 FDB-083 14.9 21.4 16.6 23.8 FDB-083S 3 / 8 18.7 26.8 20.8 29.9 FDB-084 24.9 35.7 27.8 39.7 FDB-084S ½ 26.8 38.2 29.8 42.5 FDB-162 6.4 9.3 7.1 10.3 FDB-163 15.3 21.8 17.1 24.3 FDB-163S 3 / 8 21.7 31.1 24.2 34.6 FDB-164 26.4 37.8 29.4 42 FDB-164S ½ 34 48.7 37.9 54.2 FDB-165 34.6 49.5 38.6 55.2 FDB-165S 5 / 8 46.2 65.9 51.4 73.4 FDB-303 17.1 24.3 19 27.1 FDB-304 30.1 42.9 33.5 47.7 FDB-304S ½ 35.9 51.3 40 57.1 FDB-305 38.1 54.6 42.4 60.8 FDB-305S 5 / 8 50.8 72.7 56.6 80.9 FDB-307S 7 / 8 57.2 81.8 63.7 91.1 FDB-415 47 67.2 52.4 74.8 FDB-417S 7 / 8 73 104.3 81.3 116.1 For more information, please consult technical bulletin, datasheet, operating instructions or catalogue (www.emersonclimate.eu). 8
Take Apart Liquid Line Filter Driers ADKS-PLUS ADKS: Nominal Flow Capacity, kw Connection Type ODF 0.07 0.14 0.07 0.14 bar bar bar bar ADKS-PLUS 485 16mm ( 5 / 8") 68 87 75 96 ADKS-PLUS 487 22mm( 7 / 8") 126 158 140 175 ADKS-PLUS 489 1-1 / 8" 177 227 197 252 ADKS-PLUS 4811 35mm(1-3 / 8") 247 307 275 342 ADKS-PLUS 4813 1-5 / 8" 260 329 289 366 ADKS-PLUS 4813MM 42mm 268 338 299 376 ADKS-PLUS 967 22mm( 7 / 8") 138 172 153 191 ADKS-PLUS 969 1-1 / 8" 217 260 241 289 ADKS-PLUS 9611 35mm(1-3 / 8") 264 348 294 388 ADKS-PLUS 9613 1-5 / 8" 303 407 337 453 ADKS-PLUS 9613MM 42mm 307 416 342 463 ADKS-PLUS 1449 1-1 / 8" 219 271 243 302 ADKS-PLUS 14411 35mm(1-3 / 8") 304 379 339 422 ADKS-PLUS 14413 1-5 / 8" 307 417 342 464 ADKS-PLUS 14413MM 42mm 312 424 347 472 ADKS-PLUS 14417 54mm(2-1 / 8") 364 485 405 540 ADKS-PLUS 19211 35mm(1-3 / 8") 310 381 345 424 ADKS-PLUS 19213 42mm(1-5 / 8") 342 438 381 488 ADKS-PLUS 19213MM 42mm 346 442 386 492 ADKS-PLUS 19217 54mm(2-1 / 8") 373 491 415 547 FDS (Quick Cap) FDS: Nominal Flow Capacity, kw Type FDS-245 FDS-247 Connection ODF 0.07 bar 1.4 bar 0.07 bar 1.4 bar 5 / 8"(16 mm) 65 85 72 94 7 / 8"(22 mm) 97 131 108 146 FDS-249 28 mm 98 139 109 154 FDS-249 1-1 / 8" 98 141 109 157 Nominal flow capacity rated at +30 C liquid temperature. -15 C evaporating temperature and specified pressure drop. For more information, please consult technical bulletin, datasheet, operating instructions or catalogue (www.emersonclimate.eu). 9
Liquid Line Filter Driers Correction Factors ADK, FDB, ADKS and FDS Use following simplified formula for operating conditions other than -15 C / +30 C: Q n = Q 0 x K t Q n: Nominal flow capacity Q o: Required cooling capacity K t: Correction factor for evaporating and liquid temperature Liquid temp. C : Correction Factors K t Dew Bubble Evaporating Temperature C Point point +20 +15 +10 +5 0-5 -10-15 -20-25 -30-35 -40-45 63 60 1.41 1.44 1.47 1.50 1.53 1.57 1.61 1.66 1.70 1.76 1.81 1.88 1.94 2.02 59 55 1.28 1.30 1.32 1.35 1.38 1.41 1.44 1.48 1.52 1.56 1.61 1.66 1.71 1.77 54 50 1.17 1.19 1.21 1.23 1.26 1.28 1.31 1.34 1.37 1.41 1.45 1.49 1.53 1.58 49 45 1.08 1.10 1.12 1.13 1.16 1.18 1.20 1.23 1.26 1.29 1.32 1.35 1.39 1.43 44 40 1.01 1.02 1.04 1.05 1.07 1.09 1.11 1.13 1.16 1.18 1.21 1.24 1.27 1.31 39 35 0.94 0.96 0.97 0.98 1.00 1.02 1.04 1.06 1.08 1.10 1.12 1.15 1.18 1.20 35 30 0.89 0.90 0.91 0.92 0.94 0.95 0.97 0.99 1.01 1.03 1.05 1.07 1.09 1.12 30 25 0.84 0.85 0.86 0.87 0.88 0.90 0.91 0.93 0.94 0.96 0.98 1.00 1.02 1.04 25 20 0.80 0.81 0.83 0.84 0.85 0.86 0.88 0.89 0.91 0.92 0.94 0.96 0.98 20 15 0.77 0.78 0.79 0.81 0.82 0.83 0.84 0.86 0.87 0.89 0.91 0.92 15 10 0.75 0.76 0.77 0.78 0.79 0.80 0.81 0.83 0.84 0.86 0.87 10 5 0.72 0.73 0.74 0.75 0.76 0.78 0.79 0.80 0.81 0.83 6 0 0.70 0.71 0.72 0.73 0.74 0.75 0.76 0.78 0.79 1-5 0.68 0.69 0.70 0.71 0.72 0.73 0.74 0.75-4 -10 0.66 0.67 0.68 0.69 0.70 0.71 0.72-9 -15 0.64 0.65 0.66 0.67 0.68 0.69-14 -20 0.63 0.63 0.64 0.65 0.66 Liquid Line Filter Driers Correction Factors Liquid Temp. C Correction Factors K t Dew Bubble Evaporating Temperature C Point point +20 +15 +10 +5 0-5 -10-15 -20-25 -30-35 -40-45 63 60 1.39 1.41 1.43 1.46 1.48 1.51 1.54 1.57 1.60 1.64 1.68 1.72 1.77 1.82 59 55 1.27 1.29 1.30 1.32 1.34 1.37 1.39 1.42 1.44 1.47 1.51 1.54 1.58 1.62 54 50 1.17 1.19 1.20 1.22 1.24 1.25 1.28 1.30 1.32 1.35 1.37 1.40 1.44 1.47 49 45 1.09 1.10 1.12 1.13 1.15 1.16 1.18 1.20 1.22 1.24 1.27 1.29 1.32 1.35 44 40 1.02 1.03 1.04 1.06 1.07 1.08 1.10 1.12 1.14 1.15 1.18 1.20 1.22 1.25 39 35 0.96 0.97 0.98 0.99 1.00 1.02 1.03 1.05 1.06 1.08 1.10 1.12 1.14 1.16 35 30 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 1.00 1.01 1.03 1.05 1.07 1.09 30 25 0.86 0.87 0.88 0.89 0.90 0.91 0.92 0.93 0.94 0.96 0.97 0.99 1.00 1.02 25 20 0.83 0.83 0.84 0.85 0.86 0.87 0.88 0.89 0.91 0.92 0.93 0.95 0.96 20 15 0.79 0.80 0.81 0.82 0.83 0.84 0.85 0.86 0.87 0.89 0.90 0.91 15 10 0.77 0.77 0.78 0.79 0.80 0.81 0.82 0.83 0.84 0.86 0.87 10 5 0.74 0.75 0.76 0.76 0.77 0.78 0.79 0.80 0.81 0.83 6 0 0.72 0.72 0.73 0.74 0.75 0.76 0.77 0.78 0.79 1-5 0.69 0.70 0.71 0.72 0.73 0.74 0.75 0.76-4 -10 0.67 0.68 0.69 0.70 0.71 0.71 0.72-9 -15 0.66 0.66 0.67 0.68 0.69 0.70-14 -20 0.64 0.65 0.65 0.66 0.67 10
Oil Separators OSH OSB OST Type Connection Nominal capacity kw OSH-404 1/2" 6,5 6,3 OSH-405 5/8" 17,4 16,8 OSH-407 7/8" 26,1 25,3 OSH-409 1-1/8" 34,9 33,7 OSH-411 1-3/8" 43,6 42,1 OSH-413 1-5/8" 61,0 59,0 OSH-611 1-3/8" 47,9 46,3 OSH-613 1-5/8" 61,0 59,0 OSH-642 42 mm 61,0 59,0 OSH-617 2-1/8" 98,0 94,8 OST-404 1/2" 6,5 6,3 OST-405 5/8" 17,4 16,8 OST-407 7/8" 26,1 25,3 OST-409 1-1/8" 34,9 33,7 OST-411 1-3/8" 43,6 42,1 OST-413 1-5/8" 61,0 59,0 OSB-613 1-5/8" 61,0 59,0 OSB-617 2-1/8" 98,0 94,8 Refrigerant R 407A R 407F Condensing Temperature C Correction factor Kt Evaporating temperature C +10 0-10 -20-30 -40-50 25 1,22 1,25 1,30 1,33 1,43 1,53 1,63 30 1,12 1,15 1,20 1,26 1,32 1,42 1,54 35 1,03 1,06 1,11 1,16 1,24 1,34 1,46 40 0,95 0,99 1,04 1,09 1,17 1,28 1,41 45 0,90 0,92 0,97 1,03 1,14 1,26 1,39 50 0,86 0,89 0,93 1,00 1,13 1,26 1,39 For more information, please consult technical bulletin, datasheet, operating instructions or catalogue (www.emersonclimate.eu). 11
Other Products Superheat Controllers Pressure Transmitters Fan Speed Controls EC3-X32/X33 PT5 PT6 Note: / is included in new software for production starting from November 2013 PT5-xx T FSE For EC-motors FSY for induction motors Pressure Switches With Adjustable Setpoints Pressure Switches With Fixed Setpoints PS1 PS2 PS3 PS4 Oil Level Management System, Traxoil Oil Level Monitoring Traxoil OM3 OW4 Ball Valves Moisture Indicators BVE BVS AMI MIA For more information, please consult technical bulletin, datasheet, operating instructions or catalogue (www.emersonclimate.eu). Emerson Climate Technologies GmbH shall not be liable for errors in the stated capacities, dimensions, etc., as well as typographic errors. Products, specifications, designs and technical data contained in this document are subject to modification by us without prior notice. Illustrations are not binding. The Emerson Climate Technologies logo is a trademark and service mark of Emerson Electric Co. Emerson Climate Technologies Inc. is a subsidiary of Emerson Electric Co.