IEEE Std 592 Test Program using Current Cable Accessories and Installation Practices

Similar documents
S Fault Indicators. S.T.A.R. Type CR Faulted Circuit Indicator Installation Instructions. Contents PRODUCT INFORMATION

COOPER POWER SERIES. S.T.A.R. PATHFINDER variable trip TPR faulted circuit indicator installation instructions. Fault indicators MN320003EN

COOPER POWER SERIES. S.T.A.R. Type ER faulted circuit indicator installation instructions. Fault Indicators MN320006EN

FCI LT LM UNDERGROUND

Part Number: CAT6+ UTP PVC PATCH CORDS CAT6+ Patch Cord, UTP, PVC

Primary UD EPR / LLDPE, Concentric Neutral

N-2 EDS Factory Sealed and EFS Tumbler Switches: Explosionproof, Dust-Ignitionproof UNILETS for Use with Threaded Metal Conduit.

Part Number: CAT6+ UTP PVC PATCH CORDS CAT6+ Patch Cord, UTP, PVC

Primary UD TR-XLPE / PVC, Concentric Neutral

FAQ (Frequently Asked Questions)

LP-NSM(L) Series. Features. Product Dimensions. Small size of Fast tripping resettable circuit protection

LP-NSM(L) Series. Features. Product Dimensions. Small size of Fast tripping resettable circuit protection

XL³ 400 class II insulated distribution cabinets and cable compartments

SAFETY BURNDY HYPRESS TM OPERATING & MAINTENANCE INSTRUCTIONS Y750BH 2004 FCI USA INC.

EPIC Industrial connectors

U xafaiagy10258nzw BLUING TANK STAND SYSTEM INSTRUCTIONS WARNING SETTING UP THE BLUING STANDS HEIGHT OF BURNERS GAS LINES FINAL SETUP #

Natural Gas.

Installation Instructions

Single Port Modular Jacks

MGL Avionics EFIS G2 and iefis. Guide to using the MGL RDAC CAN interface with the UL Power engines

HALE SECURITY PET DOOR CAT GUARDIAN patent pending

IQ Range. Electrical Data 3-Phase Power Supplies. Keeping the World Flowing

59-P-ID. Arcos Pendant Indirect /Direct. Ordering Guide. Key Features 59-P-ID. Fixture Type: Project Name: Quick Find litecontrol.

table of contents Personnel Protection Products SECTION L LS ECTION

CSA6. Product Specifications. SoftSound SXC 2600

XL³ 800 IP 55metal distribution cabinets, freestanding enclosures and cable compartments

Primary UD TR-XLPE Insulated, Concentric Neutral

Smart bark control collar BC-2. User manual

TURCK Industrial Wiring Solutions

TC(XHHW-2) 600 V Single core

ENGINEERING TEST SPECIFICATION

98-P-I Pendant Indirect. Ordering Guide. Key Features 98-P-I. Fixture Type: Project Name: Quick Find litecontrol.com

TPS204xB/TPS205xB Current-Limited, Power-Distribution Switches data sheet (SLVS514)

F-CONNECTORS. Keystone Jack F-Connectors

83A series Aluminium (light weight) compression fittings

Feasibility Study for the Duke Energy Florida Suwannee River Plant 214 MW Net Summer / 232 MW Net Winter 230 kv Combustion Turbine December 2013

300 Yard Trainer GDT Product Manual

Frequently Asked Questions

Operating Instruction EHP Issue 09/2016

AmpFlex Flexible Current Probes

400 Yard Trainer GDT Product Manual

83A series Aluminium (light weight) compression fittings Ø 1/ nominal pipe size, NPT thread

User s Guide. High Performance Linear Products SLOU119

Midwest Metal Fabricators LLC 712 Maple Street Wapakoneta, OH Phone (419) Fax (419)

AquaReef 200. Instruction Manual

OPERATING AND BASIC TRAINING GUIDE PLEASE READ THIS ENTIRE GUIDE BEFORE BEGINNING

Operating Guide. PBC Rechargeable Bark Control Collar. Please read this entire guide before beginning.

Y Series 4, 5 & 6 Tumbler Switchlocks

MODLINK MSDD Front Panel Interfaces

Laurelview Dog Kennel

SMARTKITTY SELFCLEANING LITTER BOX

PET DOOR IMPORTANT! READ AND FOLLOW THESE INSTRUCTIONS CAREFULLY AND KEEP FOR FUTURE REFERENCE.

Colour Codes & Cable Make Up

Super Vu-Tron Supreme Types SJOOW/SOOW

Getting Started. Device Overviews. Setting Up the Pro 550 System Before you can use the Pro 550 system, you must set up the devices.

ethercon solutions for multichannel audio, video, and mixed signal distribution* *: and more!

Table of Contents Operating Guide Training Guide

Lifting points for CLT. a practical guide

Electromagnetic flowmeters. dg: NEW. Sensors MUT 2200 EL / MUT 2500 EL DS100-4-ENG 1/14

User Manual EN: User Manual 1-32 DE: Bedienungsanleitung FR: Guide d utilisation NL: Handleiding

Sold by:

Pet Door Materials.

Barrelponics. Construction/Workflow OHIO AGRICULTURAL RESEARCH AND DEVELOPMENT CENTER

MGG Radio Controlled Hidden Fencing System for Dogs. Operator s Manual for Model no: HT-023

Brandenburg German Shepherds, Suli Domínguez, c/o N th Street, Menomonie, Wisconsin, Puppy Purchase Contract and Three-Year Health Guarantee:

PET DOOR. Deluxe Aluminium IMPORTANT! READ AND FOLLOW THESE INSTRUCTIONS CAREFULLY AND KEEP FOR FUTURE REFERENCE. Product Codes: #1168, #1169, #1170

2. From where the latest Software Development Kit for the EVM can be downloaded?

MGG Radio Controlled Hidden Fencing System for Dogs. Operator s Manual for Model no s: 023 and 023B

LAH Measuring Instructions Light Assistance Harness with Standing Handle

Your American Made Source

BUYING GUIDE ALGOT. Storage across the home. DESIGN Francis Cayouette

INNOTEK. Spray Bark Control. Operating Guide. Please read this entire guide before beginning.

2016 Elephant Seal Breeding Season Update February 26, 2016

INSTALLATION INSTRUCTIONS

Lioness Guidebook: Open Me to Get Started!

ASSEMBLY & INSTRUCTION MANUAL

Programming and Installation Guide. PPA Microchip Cat Flap. Series. Please read this entire guide before beginning.

Ultra Min No-Bark Training Collar Ultra Small Ultra Powerful Ultra Control

COMPANY PRESENTATION

Pixie-7P. Battery Connector Pixie-7P Fuse* Motor. 2.2 Attaching the Motor Leads. 1.0 Features of the Pixie-7P: Pixie-7P Batt Motor

K9K-914 Anti Bark Collar User's Manual. Introduction:

Outdoor Bark Control

REGULATIONS RELATED TO TRAWL GEAR CONFIGURATION, GEARS ALLOWED ON BOARD, AND AREA OF USE

Wall Mounted Cat Tree Instruction Manual

EVM. VERTICAL MULTISTAGE ELECTRIC PUMPS in cast iron, AISI 304, AISI 316. Your Life, our Quality. Worldwide. 36 Commercial

Product Manual. PBC Bark Collar. Please read this entire Product Manual before beginning.

Pigeon Spike Plastic Narrow Bird Spikes Includes specs for: Pigeon Spike Plastic Narrow Bird Spike and Surface Cleaning Systems.

Quality Requirements Q3R Fit Check

Pigeon Spike Composite Bird Spikes Includes specifications for: Pigeon Spike Composite Bird Spike and Surface Cleaning Systems.

GFCI Personnel Protection Devices

Portable Washing Machine GPW-5

ALL ABOUT: FOAM SEDIMENT CONTROL WATTLES

Inductive Proximity Switches

HaloGLS, HaloCandle and HaloSpherical lamps

Fiber-Optic Accessories

Product Manual. ZAL Simply Clean Automatic Litter Box. Please read this entire Product Manual before beginning.

Dogs On Course in North America, LLC Agility Equipment Specifications

Vertebrate Pest Management

Feral Poultry: How to Construct a User-Friendly Trap

E-Collar Technologies, Inc. 400/402 Owner's Manual Happiness is a Well Behaved Dog

Transcription:

IEEE Std 592 Test Program using Current Cable Accessories and Installation Practices Thomas J. Parker GTRC 1

Notice a. The material contained herein is, to our knowledge, accurate and reliable at the date of publication. b. It is provided for the overall benefit of the electric energy delivery industry. c. It shall not be construed as an endorsement of any project, process or provider by the author nor the organizations sponsoring this work. d. Neither the author nor the organizations sponsoring this work shall be responsible for any injury to or death of persons or damage to or destruction of property or for any other loss, damage or injury of any kind whatsoever resulting from the use of the project results and/or data. e. The author and the organizations sponsoring this work disclaim any and all warranties, both express and implied, with respect to analysis or research or results contained in this material. f. It is the user's responsibility to conduct the necessary assessments in order to satisfy themselves as to the suitability of the products or recommendations provided in this material. 2

Joint Jacket Restoration Phase I During revision of IEEE Std 592-2007, concern arose over the impact of jacket restoration practices on the ability of the semiconductive exterior of joint housings to initiate faults 25 kv rated cable joints, with and without jacket restoration, were fault-tested according to the Standard to determine if the covering adversely affected the device s ability to meet the minimum requirement for initiating faults. 3

Fault Tests Phase I Conducted at Power Laboratory A Four Samples Each of Four Sample Types Bare Joint Hand Taped Re-jacketed Joint Cold Shrink Re-jacketed Joint Heat Shrink Re-jacketed Joint Samples assembled using premolded joints, 25 kv MV cable with 1/0 AWG conductor and a PE jacket, and various jacket restoration materials IEEE 592 Section 4.3, Fault Current Initiation Test 10 ka for 10 cycles, 2 operations 4

Typical Jacket Restoration Samples Phase I Hand Taped Heat Shrink Cold Shrink None 5

Fault Test Phase I Drain Wire Vaporized Neutral Wires Burned in Two Typical Non-Jacketed Sample After Fault 1 6

Fault Test Phase I Joint Insulation Shield Exposed Fault Rod Typical Hand Taped Sample After Fault 2 7

Results Phase I All test samples successfully initiated two consecutive fault current arcs as required by the Standard. The application of jacket restoration may have improved performance. 8

Limited information provided in Standard: erosion resistant metal, such as copper-tungsten, 3/8- inch in diameter, and threaded at one end to engage the accessory connector through a drilled hole not to exceed 3/8-inch in diameter copper-tungsten alloys are available that vary from 55 % tungsten / 45 % copper to 80 % tungsten / 20 % copper in various ratios An alloy consisting of 56% tungsten and 44 % copper was chosen for this test program Same alloy used for Phase II Fault Rod Selection 9

No information provided in Standard 9/16 die size (top) 11/16 inch O.D. 3/8 inch I.D. same as outside diameter of rod limited engagement of rod threads 840 die size (bottom) used in samples tested Same connector used for Phase II Connector Selection 10

Additional Construction Issues Fault rod location on joint Illustration in standard shows fault rod installed in center of the joint on the side opposite the attachment eyes for the shield drain wires For the premolded joints initially supplied, that location put the fault rods through the injection molding port Joint body stretched when installed opening up the diameter of the hole drilled for the fault rod leaving gaps around the rod 11

Additional Construction Issues Gap Test samples remade using an available different premolded joint housing design to assure tight fit on the fault rod and relocating the fault rod to not pass through the injection port 12

Areas of Investigation Phase II Semiconductive Shield Resistance Measurements: IEEE 592 contains a test procedure and minimum requirements for the semiconductive shield resistance of cable accessories. How do the samples we are testing measure up? Does the test seem adequate? 4 kv systems: IEEE 592 fault initiation tests on 15 kv rms φ φ rated system components are tested according to their intended use voltage. However, these systems are also often operated in service at 4 kv rms φ φ. Does fault initiation still occur on these lower voltage systems? Elbows: The installation of a Faulted Circuit Indicator (FCI) increases the gap between an elbow and the cable metallic shield. Does this increased gap affect the initiation of a fault when an elbow failure occurs? 13

Resistance Measurements on Semiconductive Shields All measurements made according to requirements in the IEEE 592 Standard using four-wire resistance measurements with silver paint and / or copper braid electrodes. 14

Resistance Measurements on Semiconductive Shields Summary Samples Average Resistance (Ω) Before Aging After 21 Days Aging @ 121 C @ 20 C @ 90 C @ 20 C @ 90 C Joints 378 169 171 132 Elbows 186 162 59 52 Cable IS 378 1257 208 509 All measurements made according to requirements in the IEEE 592 Standard using silver paint and / or copper braid electrodes. Both joints and elbows met the requirement in the Standard that the resistance be 5000 Ω. Cable Insulation Shield (IS) measurements reported for information only. 15

Fault Tests Phase II at High Power Lab B Four Sample Types 1. Bare Joint 2. Re-jacketed Joint 3. Standard Elbow 4. FCI Elbow (3-inch jacket and neutral cutback below elbow cable entrance for FCI installation) 16

Cable Joint Configurations Tested Exposed Semi-conductive Shield RE-JACKETING MATERIAL, HEAT-SHRINK, COLD-SHRINK, OR HAND -TAPED Jacket Material Installed Over Semi-conductive Shield 17

Separable Insulated Connector Test Configurations Standard Elbow Test Configuration FCI Elbow Test Configuration 18

Fault Test Plan Use first sample of each sample type to determine voltage needed for repeated faults Apply 1.8 kv rms φ G for first attempted fault If necessary, increase applied voltage in 0.5 kv rms steps until sample faults each time voltage is applied Use that test voltage for testing remaining two samples (target is three faults each of 10 ka rms for 10 cycles) 19

Bare Joint Fault Test Setup Current Path Insulating Phenolic Frame No Connection Source Connections Fault Rod Bare Joint Sample (JB2) Ready for Test 20

Bare Joint Fault Test Did Not Try to Initiate Third Neutral Exiting Cable Jacket Damaged Cable Conductor Destroyed Fault Bare Joint Sample (JB2) After Fault 2 21

Sample JB2 Dissection Source Connection Removal of joint body reveals no damage inside joint (neutral bent back in place) 22

Joint Fault Test Summary BARE JOINTS Sample Fault Comments JBD (Dummy) 1 2 JB2 1 2 JB3 1 2 JB6 1 Took 4.3 kv rms ɸ-G to get second fault Seven shots on sample by 2 nd fault last shot with much higher current than 10 ka Did not try 3 rd shot Cable conductor connection destroyed and neutral partially destroyed on sample source end during 2 nd fault All faults at 4.3 kv rms ɸ-G Could not try 3 rd shot Cable conductor connection and neutral connection on source end destroyed during 2 nd fault All faults at 4.3 kv rms ɸ-G Could not try 3 rd shot Cable conductor connection destroyed and neutral partially destroyed on sample source end during 1 st fault All faults at 4.3 kv rms ɸ-G Could not try 2 nd shot 23

Re-jacketed Joint Fault Test Setup Re-jacketed joint sample (JC7) ready for test 24

Re-jacketed Joint Fault Test HS Video for JC7, Fault 1 4.3 kv rms φ-g 14-225 Videos\16906_A99_023.mp4 Tried but Did Not Initiate Second Fault 25

Sample JC7 Dissection Source Connection Removal of joint housing reveals severe damage inside joint / no fault rod 26

Joint Fault Test Summary RE-JACKETED JOINTS Sample Fault Comments JC1 1 2 Cable semicon damage present at source end of joint All faults at 4.3 kv rms ɸ-G No fault initiated on 3 rd shot JC6 1 2 3 All faults at 4.3 kv rms ɸ-G JC7 1 Fault rod, cable, conductor, and connector severely damaged inside joint during 1 st shot All faults at 4.3 kv rms ɸ-G No fault initiated on 2 nd shot 27

Summary All Joint Tests 4.3 kv ɸ-G required for multiple fault initiation Some faults did not initiate until many cycles into the three seconds of voltage application. Some faults self-extinguished before the required 10 cycles were complete. Some restrikes did occur resulting in a second fault within the allotted three-second voltage application. Third fault on bare samples occurred on zero of four tested. Arc destroyed source sample connections on three of four samples. Third fault on jacket restoration samples occurred on one of three samples tested. 28

Elbow Fault Test Setup Fault Rod Current Path Source Connections Typical Elbow Sample Ready for Test 29

Standard Elbow Fault Test (1 of 2) HD Video for END (Dummy Sample), Fault 1 1.8 kv rms φ-g 14-225 Videos\14-225 Sample END TRC025.mp4 Sample Damaged Too Much to Continue Using It for Testing 30

Standard Elbow Fault Test (2 of 2) HS Video for EN6, Fault 3 3.4 kv rms φ-g 14-225 Videos\16906_A99_030.mp4 31

Elbow Fault Test Summary STANDARD ELBOWS Sample Fault Comments END (Dummy) 1 EN6 1 2 3 No fault at 1.8 kv rms ɸ-G / sample caught fire and had to be put out with extinguisher No further testing possible Required 3.4 kv rms ɸ-G to get 1 st fault Remaining faults also at 3.4 kv ɸ-G EN7 1 2 3 All faults at 3.4 kv rms ɸ-G EN1 1 2 3 All faults at 3.4 kv rms ɸ-G 32

FCI Elbow Fault Test Setup Fault Rod FCI Installation Area FCI Elbow Sample Ready for Test (Sample EF3) 33

FCI Elbow Fault Test HD Video for EF3, Fault 1 [With Restrike] 3.8 kv rms φ-g 14-225 Videos\14-225 Sample EF3 TRC043.mp4 34

FCI Elbow Fault Test 15.0 kamps 16906_A99_043 Sample Curr P1 1-5.350 Amps 2 7.812 Amps -15.0 kamps 6.0 kv Sample Volt P1 1 4.708 kv 2 3.637 kv -6.0 kv 44.85 s 500.0 ms/div 47.40 s FCI Elbow Sample (EF3) Fault 1 Waveforms 35

Sample EF3 Examination / Dissection Severe cable semicon damage below elbow. Did not try additional faults Neutral connection below elbow and exposed cable neutrals destroyed 36

Elbow Fault Test Summary FCI ELBOWS Sample Fault Comments EF6 1 2 3 EF2 1 2 EF3 1 First fault occurred at 3.3 kv ɸ-G Took 3.8 kv rms ɸ-G to get 2 nd fault Remaining fault at 3.8 kv ɸ-G All faults at 3.8 kv rms ɸ-G Elbow blown off of cable on 2 nd fault Could not try 3 rd shot 1 st Fault at 3.8 kv rms ɸ-G Ground below elbow destroyed by 1 st fault and cable semicon severely damaged Did not try 2 nd shot EF8 1 2 3 All faults at 3.8 kv rms ɸ-G 37

Summary All Elbow Tests Fault rod NOT in location shown in the Standard which likely lowered the required fault initiation voltage. Too low voltage (1.8 kv rms ɸ-G) caused the one sample tested at that voltage to catch on fire. 3.4 kv rms ɸ-G required for multiple faults on standard samples 3.8 kv rms ɸ-G required for multiple faults on FCI samples Some faults self-extinguished before the required 10 cycles were complete. Three faults achieved on standard samples. Three faults on FCI samples achieved on two of four samples tested. Remaining samples were damaged during testing so that tests could not be continued. 38

Overall Summary / Conclusions (1 of 2) 4 kv System Operation: Joints tested required 4.3 kv rms φ-g minimum to initiate multiple faults. Elbows tested required 3.4 kv rms φ-g minimum to initiate multiple faults. (Note that this may be a lower required fault initiation voltage due to the change in the fault rod location over that of the location identified in the Standard.) IEEE Std 592 specifies testing these accessories at 7.0 kv rms φ-g. The semiconductive shields of the accessories tested would not initiate faults on a 4.2 kv rms φ φ system. 39

Overall Summary / Conclusions (2 of 2) Cable Jacket and Metallic Shield Cutback for FCI Use: FCI cutbacks below elbows increase the voltage required to initiate a fault over that of a standard elbow installation. Considerable damage is done to the cable in this area when a fault occurs. 40

Additional Issues Fault Rod Do we need to provide more information regarding the selection of fault rods? Where should the fault rod be located in elbows? Connector Selection Do we need to provide information on the selection of connectors to use in joint test samples? Joint Body Stretching/Fault Rod Contact with Accessory Body What, if anything do we need to include in the standard about this topic? Sample Construction Neutrals Should the neutral be overlapped onto the accessory under test as shown in the diagrams in IEEE 592 or should the accessory be installed per manufacturer instructions? 41

Additional Issues X/R Ratio What should the X/R ratio of the test circuit be since it is currently not defined? (These tests used an X/R of 17) IEEE 386-2006 uses an X/R of 6 for 200 A rated connectors and an X/R of 20 for 600 A rated connectors for the short-time current tests. IEEE 404-2012 does not specify an X/R ratio for the shorttime current tests. Acceptable Fault What defines an acceptable 10-cycle fault as required by IEEE 592? (Some faults will self-extinguish after a few cycles and then may reform.) 42

Questions? 43